Experimental investigation of single phase convective heat transfer coefficient in a corrugated plate heat exchanger for multiple plate configurations

T. S. Khan, M. S. Khan, Ming C. Chyu, Z. H. Ayub

Research output: Contribution to journalArticlepeer-review

156 Scopus citations

Abstract

Corrugated plate heat exchangers have larger heat transfer surface area and increased turbulence level due to the corrugations. In this study, experimental heat transfer data are obtained for single phase flow (water-to-water) configurations in a commercial plate heat exchanger for symmetric 30°/30°, 60°/60°, and mixed 30°/60° chevron angle plates. Experiments were carried out for Reynolds number ranging from 500 to 2500 and Prandtl number from 3.5 to 6.5. Experimental results show significant effect of chevron angle and Reynolds number on the heat transfer coefficient. Based on the experimental data, a correlation to estimate Nusselt number as a function of Reynolds number, Prandtl number and chevron angle has been proposed.

Original languageEnglish
Pages (from-to)1058-1065
Number of pages8
JournalApplied Thermal Engineering
Volume30
Issue number8-9
DOIs
StatePublished - Jun 2010

Keywords

  • Chevron angle
  • Heat transfer
  • Nusselt number
  • Plate heat exchanger
  • Single phase

Fingerprint

Dive into the research topics of 'Experimental investigation of single phase convective heat transfer coefficient in a corrugated plate heat exchanger for multiple plate configurations'. Together they form a unique fingerprint.